TRAINING
iGUARD Troubleshooting
Specific Error Displays
Listing
of all error and warning messages in the iGUARD controller.
J1939 Suspect Parameter
Number (SPN) Displays
J1939 Failure Mode Indicator
Number (FMI) Displays
Specific
Error Displays
If
the iGUARD is showing specific warning or fault information, it
is usually pretty straightforward (i.e. SENDER OPEN means that
the sender is not providing a current path to ground, or SENDER
SHORTED meaning that a senders resistance is below the minimum
limit) However, there are some messages that are rare or could
make use of further explanation. The full listing of all errors
and their various explanations are below.
- "AC
CURRENT TOO HIGH" - The setpoint for the AC current has
been exceeded. If this is the cause of shutdown, the AC current
remained higher than the instantaneous overcurrent setpoint for
longer than the bubble timer setting.
- "AC
FREQUENCY HIGH" - The setpoint for the AC frequency has
been exceeded. If this is the cause of shutdown, the AC frequency
remained too high for longer than the bubble timer setting.
- "AC
FREQUENCY LOW" - The setpoint for the AC frequency has been
exceeded. If this is the cause of shutdown, the AC frequency
remained too low for longer than the bubble timer setting.
- "AC
VOLTAGE TOO HIGH" - The setpoint for the AC voltage has
been exceeded. If this is the cause of shutdown, the AC voltage
remained too high for longer than the bubble timer setting.
- "AC
VOLTAGE TOO LOW" - The setpoint for the AC voltage has been
exceeded. If this is the cause of shutdown, the AC voltage remained
too low for longer than the bubble timer setting.
- "AIR
DAMPER CLOSED" - The digital input connected to the air
damper position switch (the switch makes when the air damper
closes) is active. As long as this input is active, the engine
will not attempt to start, as the engine cannot run with it's
air source cut off.
- "AIR
FILTER BLOCKED" - The digital input connected to an air
filter differential pressure gage (typically a Murphy DP20 series
differential pressure gage) is made. This indicates that the
pressure differential across the filter is too high, and the
filter media should be replaced. This is a warning only and will
not keep the set from running, however, running a set with a
clogged air filter will degrade performance, load capacity, and
reliability.
- "AIR
TEMP. HIGH" - The setpoint for the external air ambient
temperature has been exceeded.
- "AUTO" -
The screen displays this to let the user know that it is in AUTO
start mode, and is waiting for a remote start signal. The controller
constantly 'watches' a digital input and/or a Modbus register,
and when the digital input goes active, or the Modbus register
becomes TRUE, the controller initiates an automatic start sequence
.
- "AUTOSTART" -
This message indicates that an automatic starting sequence is
happening.
- "B2B
COMMUNICATION ERROR" - This message indicates that the interboard
communications (between the user interface board, I/O board or
the energy monitoring board) has failed. While it is possible
to cycle power and recover from a truly random event, this serious
error usually indicates a board set with a hardware problem.
If you see this and it either won't clear with a power cycle,
or if it clears and then reoccurs, please contact FW Murphy Technical
Services at (918) 317-4100
- "BATTERY
CHARGER FAILED" - In NFPA applications, a conforming external
battery charger has a dry contact that is held energized anytime
the output voltage is correct. This contact will transfer (the
relay will de-energize) if the charger loses power, or the output
fails or drops below the minimum proper voltage. This message
is displayed if the digital input tied to the charger contact
is in the "fault" (active) position. This is a warning only indication
and the set will start and run even with this fault active.
- "BATTERY
VOLTAGE HIGH" - The setpoint for the battery charge voltage
high limit has been exceeded. This indicates that the battery
is receiving a charge voltage that is greater than the maximum
recommended, and that battery damage may start to occur. While
this error will not keep the set from starting and running, overcharging
the battery will shorten its life dramatically.
- "BATTERY
VOLTAGE LOW" - The setpoint for the battery charge voltage
low limit has been exceeded. The battery voltage is approaching
a lower limit where it may not have sufficient capacity to crank
and start the engine, thus it can seriously affect reliability.
This message is typically seen with systems that either do not
have an external charger, or are not load tested often enough
to maintain proper battery charge.
- "BATTERY
WEAK:FAILED" -
The setpoint for the minimum battery voltage during cranking
has been exceeded. The battery voltage falling below the setpoint
can indicate a bad battery cell, oxidized or improper connections,
or some other cranking system fault. This message is typically
seen with systems that have a battery that is either failing
or will fail shortly.
- "CHX
SENDER OPEN" - The sender attached to this channel is not
registering as there. The variable precision current drive is
unable to adjust low enough to get the measured voltage into
the proper operating range for the exact make and model of sender
attached to this channel. Typically, this message indicates that
the wiring is disconnected, cut or crushed and the sender cannot
bee "seen" by the controller. A unit displaying this message
cannot be started until the error is cleared.
- "CHX
SENDER SHORTED" - The sender attached to this channel is
registering as a short to ground. The precision current drive
is unable to adjust high enough to get the measured voltage into
the proper operating range for the exact make and model of sender
attached to this channel. Typically, this message indicates that
the wiring is shorted to ground somewhere and the sender cannot
bee "seen" by the controller. A unit displaying this message
cannot be started until the error is cleared.
- "COOLANT
LEVEL LOW" - The digital input connected to the coolant
level switch (the switch makes when the coolant level is too
low) is active. As long as this input is active, the engine will
not attempt to start, as the engine cannot run safely with no
coolant.
- "CRANK
COOLDOWN" - The engine has cranked for the preprogrammed
crank time, and the starter motor is now cooling for the pre
programmed time. (Also called CRANK REST)
- "CRANK
RETRIES EXCEEDED" - Also commonly called "OVERCRANK" - the
set tried to automatically start the programmed number of crank
cycles, but did not succeed in the allotted number of tries.
This error will cause a lockout, and require the controller to
be reset before the set can be started and run.
- "DEBUG
WARNING 00" - Internal diagnostic indicator. If you see
this message displayed, please call Murphy Technical Services
(918) 317-4100
- "DIGITAL
INPUT X" - This message indicates that one or more of the
digital inputs is/are active. Depending on what the inputs are
programmed for this may act as an immediate warning, a warning
after a delay, an immediate shutdown, or a shutdown after a delay.
If you are experiencing nuisance shutdowns or warnings and the
status/warning or history screens indicate that the cause is
one of the digital inputs, see the section under "Total System" #18
Troubleshooting digital inputs" The value of "X" is from 1 to
24.
- "ECU
ENGINE SHUTDOWN" - This message indicates that the set stopped
because the ECU on the engine caused a shutdown. This message
means that the engine ECU itself - not the iGUARD - stopped the
set operation.
- "ECU
ENGINE WARNING" - This message indicates that the ECU has
issued a warning that at least one engine parameter is in a warning
condition. It comes from the ECU. Further information on the
exact warning can be found in the iGUARD controller screen "J1939
Status"
- "ECU
NOT RESPONDING" - This message indicates that the iGUARD
is not communicating with the ECU - typically because the ECU
is powered off, the communications wires are not connected (or
not connected properly), there is no terminating resistor in
the J1939 wiring, the ECU control relay on the iGUARD is not
programmed correctly or something similar.
- "ECU
WAIT TO START" - This message means that the ECU is issuing
a wait to start command. Typically this means that the ECU is
controlling any preheating or glow plug type devices that are
needed to ensure the engine can start. The iGUARD will not crank
until the ECU wait to start message has cleared.
- "ENERGIZE
TO STOP ACTIVE" - This message means that a relay programmed
for an "Energize to stop" application is active. The energized
to stop relay is controlled by a programmable timer. When the
set no longer has a valid call to run, and any cooldown or power
good timers have expired, the relay is turned on and the counter
begins to count down. This timer state (as all programmable timers)
can be observed on the bottom line of the STATUS/WARNING page
of the iGUARD display.
- "ENGINE
COOLDOWN" - This message indicates that that the controller
has lost the remote call to run signal, and that it can begin
a cooldown. This timer allows the engine to run unloaded for
a pre-programmed time to allow the various engine parts (turbocharger,
exhaust headers etc.) time to cool down to maximize life. This
timer state (as all programmable timers) can be observed on the
bottom line of the STATUS/WARNING page of the iGUARD display.
- "ENGINE
NOT READY CRK" - This message indicates that a digital input
programmed for crank cut is active. Typically it is used as a
NFPA required secondary crank disconnect, when the set doesn't
have a magnetic pickup (AC speed sensing). It usually is connected
to a N.O. (closes on pressure rise) oil pressure switch.
- "ENGINE
NOT READY MAG" - This message indicates that the engine
is not ready to start (or to recrank in the case of a false start)
because there is a signal coming into the controller through
the magnetic pickup input that indicates that the engine is still
turning.
- "ENGINE
NOT READY RPM" - This message indicates that the engine
is not ready to start (or to recrank in the case of a false start)
because there is an RPM value coming into the controller from
the ECU that indicates that the engine is still turning.
- "ENGINE
SPEED TOO HIGH" - As a warning/status message, this indicates
that the overspeed setpoint for the engine RPM has been exceeded.
As an ES (Error Stop) message - the cause of shutdown - the engine
RPM remained too high for longer than the bubble timer setting.
- "ENGINE
SPEED TOO LOW" - As a warning/status message, this indicates
that the underspeed setpoint for the engine RPM has been exceeded.
As an ES (Error Stop) message - the cause of shutdown - the engine
RPM remained too low for longer than the bubble timer setting.
- "ENGINE
TEMP. TOO HIGH" - As a warning/status message, this indicates
that the high coolant temperature warning setpoint for the engine
has been exceeded. As an ES (Error Stop) message - the cause
of shutdown - the engine coolant temperature exceeded the high
coolant temperature shutdown setpoint.
- "ENGINE
TEMP. TOO LOW" - As a warning/status message, this indicates
that the low coolant temperature warning setpoint for the engine
has been exceeded.
- "E-STOP
(DI) N/C" - An emergency stop switch connected to this digital
input has OPENED from ground, causing the set to shutdown and
lock out. This input must be maintained closed to ground for
the set to be able to run.
- "E-STOP
(DI) N/O" - An emergency stop switch connected to this digital
input has CLOSED to ground, causing the set to shutdown and lock
out. This input must be ungrounded for the set to be able to
run.
- "E-STOP
(J8)" - This message indicates that the normally closed
emergency stop switch connected between terminals J8-1 and J8-2
has been opened. Since there must be continuity between J8-1
and J8-2 to provide power to the onboard relays, the controller
will be unable to stop an energized to stop type output, and
should only be used with energized to run - power to the fuel
solenoid, governor, or ECU - systems.
- "FORCED
RELAYS" - This message indicates that the user is in the
I/O status screen and is manually controlling the various relays.
- "FUEL
FILTER BLOCKED"" - The digital input connected to a
fuel filter differential pressure gage (typically a Murphy DP20
series differential pressure gage) is made (active). This indicates
that the pressure differential across the filter is too high,
and the filter media should be replaced. This is a warning only
and will not keep the set from running, however, running a set
with a clogged fuel filter will degrade performance, load capacity,
and reliability.
- "FUEL
LEAKING" - The digital input connected to a remote fuel
leak device is made. (active). This message indicates that there
is a fuel leak in the fuel containment basin, and that it is
unsafe to start the engine, due to a fire hazard.
- "FUEL
LEVEL HIGH" - This ES (Error Stop) message - the cause of
shutdown - indicates that the fuel level exceeded the high fuel
level shutdown setpoint.
- "FUEL
LEVEL LOW" - As a warning/status message, this indicates
that the low fuel level warning setpoint for the system has been
exceeded. As an ES (Error Stop) message - the cause of shutdown
- the fuel level exceeded the low fuel level shutdown setpoint.
- "FUEL
PRESSURE HIGH" - This ES (Error Stop) message - the cause
of shutdown - indicates that the fuel pressure exceeded the high
fuel pressure shutdown setpoint.
- "FUEL
PRESSURE LOW" - As a warning/status message, this indicates
that the low fuel pressure warning setpoint for the system has
been exceeded. As an ES (Error Stop) message - the cause of shutdown
- the fuel pressure exceeded the low fuel pressure shutdown setpoint.
- "GEN.
STEERING CHANGED" - One or more of the digital inputs connected
to an auxiliary contact on the users voltage reconnect switch
changed states (made or opened) while the set was running. Since
reconnecting under load can cause catastrophic equipment damage,
any change of state while in any mode other than waiting to start
will cause an immediate shutdown and lockout.
- "GENERATOR
NOT READY VLT" - This message indicates that the engine
is not ready to start (or to recrank in the case of a false start)
because there is an AC speed signal coming into the controller
through the energy monitor board that indicates that the AC alternator/engine
is still turning.
- "IDLE
BYPASS " - This message indicates that the digital input
programmed for this function is active. While in idle bypass
mode, the underspeed, underfrequency, and undervoltage warnings
and alarms are bypassed, and any relay programmed for idle mode,
is active. (For more details, see the
section on mechanical engines or electronic engines labeled "Problems
with Run/Idle Mode")
- "IGUARD
IS LOCKED IN MANUAL MODE ONLY" - This message indicates
that the user setup (or 'profile') has been configured such that
there is no AUTO start mode. The unit may only be controlled
by the START/STOP keyswitches, or by digital inputs selected
to mimic the keypad with user provided switches. The only way
to get an autostart mode is to reprogram the iGUARD with the
iGCON software tool
- "KVA
LIMIT EXCEEDED" - The total kVA (Volts x Amps) has exceeded
the setpoint.
- "LOAD
BYPASS ACTIVE" - This message indicates that the programmable
bubble timer is active, and is temporarily disabling overcurrent
and kVA shutdowns. The load bypass timer starts timing at the
expiration of the warmup timer, and is intended to allow a large
block load to be picked up without causing nuisance shutdowns
or causing the overcurrent setpoint to be excessive to get past
the inrush current requirements to pickup the load.
- "LOST
COMMUNICATION" - This message indicates that while connected
to a remote computer through the modem port, the communications
were lost and that no changes were saved.
- "LOW
LUBE LEVEL" - This message indicates that the digital input
programmed for this function is active. This is an immediate
stop, and if active, will not allow the set to start.
- "MAINT.
REQUIRED!" - This message indicates that one or more of
the maintenance timers has expired, and the appropriate consumable
(oil, oil filter, air filter etc.) needs to be replaced or standard
maintenance performed. To reset the maintenance timers see the
iGUARD IOM.
- "MANUAL
STOP" - This message indicates that the red manual stop
button has been pushed while in the manual or automatic mode.
- "MANUAL" -
This mode means that the controller will only start and stop
based on the front panel pushbuttons. It will ignore any remote
start demands from either a digital input or from a Modbus register.
- "MUST
BE IN MANUAL FOR LOCAL START!!" - This message is displayed
when the manual start (Green) button is pressed while the controller
is in AUTO. It is an information only message and does not change
any operating modes.
- "NO
CALL TO RUN" - This message is displayed when the remote
start demand is removed, and the iGUARD sequences through the
normal stopping process.
- "NO
OIL PRESSURE SENDER" - This message is shown on applications
with mechanical engines where the controller is not setup correctly.
It indicates that no analog channel has been selected for the
oil pressure sender. The engine will not start while this message
is displayed.
- "NO
TEMPERATURE SENDER" - This message is shown on applications
with mechanical engines where the controller is not setup correctly.
It indicates that no analog channel has been selected for the
engine coolant temperature sender. The engine will not start
while this message is displayed.
- "NO
WARNINGS ACTIVE" - This message is shown on the WARNING/STATUS
screen when there are no active warnings or shutdowns.
- "NOT
IN AUTOMATIC MODE" - This message is displayed when the
iGUARD is not in AUTO mode. NFPA-110 & NFPA-99 require that
the not in auto warning trip the common alarm - Alerting the
user that the system will not start automatically if it is left
as is. The only way to clear this alarm is to put the set back
in AUTO or to use the iGCON software tool to disable AUTO mode.
- "NOT
READY TO START" - This message indicates that the engine
is not ready to start because it has not wound down to zero RPM/freq
since the engine was turned off. This message will self clear
when the engine reaches no RPM/freq.
- "NOTHING
LOGGED" - This message is displayed on the SHUTDOWN HISTORY
screen when it has been cleared after powerup if it is set to
log all events, or if there have been no Error Stops (ES) since
the last time it was reset, if the controller is set to log only
Error Stops.
- "OIL
FILTER BLOCKED" - The digital input connected to an oil
filter differential pressure gage (typically a Murphy DP20 series
differential pressure gage) is made. This indicates that the
pressure differential across the filter is too high, and the
filter media should be replaced. This is a warning only and will
not keep the set from running, however, running a set with a
clogged oil filter will degrade performance, load capacity, and
reliability.
- "OIL
LEVEL LOW" - The digital input connected to the oil level
switch (the switch makes when the oil level is too low) is active.
As long as this input is active, the engine will not attempt
to start, as the engine cannot run safely with no oil.
- "OIL
LEVEL TOO HIGH" - The digital input connected to the oil
level switch (the switch makes when the oil level is too high)
is active. This is a warning indication only, and will not prevent
the set from running.
- "OIL
PRESSURE LOW"" - As a warning/status message, this
indicates that the low oil pressure warning setpoint for the
engine has been exceeded. As an ES (Error Stop) message - the
cause of shutdown - the engine oil pressure fell below the low
oil pressure shutdown setpoint.
- "OIL
TEMP. HIGH"" - As a warning/status message, this indicates
that the high oil temperature warning setpoint for the engine
has been exceeded. As an ES (Error Stop) message - the cause
of shutdown - the engine oil temperature exceeded the high coolant
temperature shutdown setpoint.
- "P.F.
LIMIT EXCEEDED" - As a warning/status message, this indicates
that the power factor limit warning setpoint for the set has
been exceeded. As an ES (Error Stop) message - the cause of shutdown
- the power factor exceeded the power factor limit shutdown setpoint
for longer than the duration of the nuisance timer.
- "PARAMETERS
HAVE BEEN RESET TO FACTORY DEFAULT" - This message indicates
that the user has reset the user configuration that was in the
iGUARD to the factory default.
- "POWER
FAIL OR UNKNOWN" - This message appears in the SHUTDOWN
HISTORY when the system stopped for an indeterminate reason.
- "POWERED
DOWN STANDBY" - This message appears on the iGUARD display
when the low power standby is active (The standby timer is both
enabled, and has counted down to zero) The iGUARD turns the power
off to as much of itself as it can (including the blue LED backlight
on the display) and waits for a remote start contact. If it receives
a remote contact it immediately turns everything back on and
initiates a start sequence. If the system needs to be started
manually from the standby state, the user will have to press
the start button twice - once to 'wake up' the controller, and
then again to start it.
- "PRESS
ACK/ALARM AGAIN TO RESET IGUARD" - This message is specifically
to let the user know that if they want to reset the iGUARD after
a fault (Error Stop) shutdown, they must press the acknowledge
alarm key again to return the iGUARD to a state where it can
run.
- "REVERSE
POWER DETECTED" - This message indicates that all the CT's
are wired the same, but that they are reversed with respect to
forward AC current flow OUT of the generator.
- "REVERSE
POWER PHASE A" - This message indicates that the CT for
this one phase is either truly flowing backwards (NOT likely!),
the CT is reversed with respect to the other two, or there is
a problem with the order of the CT's or the voltage connections.
- "REVERSE
POWER PHASE B" - This message indicates that the CT for
this one phase is either truly flowing backwards (NOT likely!),
the CT is reversed with respect to the other two, or there is
a problem with the order of the CT's or the voltage connections.
- "REVERSE
POWER PHASE C" - This message indicates that the CT for
this one phase is either truly flowing backwards (NOT likely!),
the CT is reversed with respect to the other two, or there is
a problem with the order of the CT's or the voltage connections.
- "RUN
TO DESTRUCT" - This message indicates that a digital input
programmed for control of the run to destruct function is active.
There is a trace that also must be cut to enable this. This mode
of operation disables all shutdowns, allowing the unit to be
used in applications where a "Battle Short" or "Run to destruction" mode
is required.
- "STANDBY
IN>" - This message show the remaining time on the standby
timer. When the timer reaches zero, it will cause the iGUARD
to enter the "POWERED DOWN STANDBY" mode. (See that entry for
more details.
- "STARTUP
BYPASS TIMER" - This message shows the time remaining that
the warnings and shutdowns typically active when starting a set
are ignored. After this timer reaches zero, any shutdowns
and warnings will perform normally.
- "STOP
PRESSED" - This message indicates that the red STOP button
has been pressed and the iGUARD will go through a shutdown sequence.
- "YOU
NEED HIGHER ACCESS LEVEL" - This message is displayed when
the user is attempting to do or change something and they do
not have a high enough password.
- "RESETTING
IGUARD" - This message is displayed when the user has pressed
ACK / ALARM after an Error Stop (ES) to get the unit back into
a mode where it can be started.
J1939
Suspect Parameter Number (SPN) Displays
In
cases where the iGUARD is connected to an ECU equipped engine,
the iGUARD will show of text-translated active fault code (FM1)
messages for both warnings and shutdowns. These are taken directly
from the J1939 standard and the SPN (Suspect Parameter Number)
for the 'standard' messages that the iGUARD displays are below:
1. "SPN:"
2. "ENGINE
SPEED",
3. "BATTERY
VOLT. SWITCHED",
4. "FUEL
DELIVERY PRESSURE",
5. "FUEL
LEVEL",
6. "ENGINE
OIL LEVEL",
7. "ENGINE
OIL PRESSURE",
8. "ENGINE
COOLANT TEMP.",
9. "ENGINE
- PERCENT TORQUE",
10. "ENGINE
- STOP LAMP",
11. "ENGINE
- WARNING LAMP",
12. "ENGINE
- PROTECT LAMP",
13. "ENGINE-
MALFUNCTION LAMP",
14. "ACCEL.
PEDAL POS.",
15. "COOLANT
LEVEL",
16. "NO
MESSAGE AVAILABLE",
J1939
Failure Mode Indicator Number (FMI) Displays
In
cases where the iGUARD is connected to an ECU equipped engine,
the iGUARD will show of text-translated active fault code (FM1)
messages for both warnings and shutdowns. These are taken directly
from the J1939 standard and the FMI (Failure Mode Indicator) for
the 'standard' messages that the iGUARD displays are below:
1. "FMI:",
2. "J1939
MESSAGES [] ",
3.
DATA VALID BUT ABOVE NORM. OPERATIONAL RANGE- MOST SEVERE LEVEL",
4.
DATA VALID BUT BELOW NORM. OPERATIONAL RANGE- MOST SEVERE LEVEL",
5. "DATA
ERRATIC, INTERMITTENT, "R INCORRECT",
6. "VOLTAGE
ABOVE NORMAL OR SHORTED TO HIGH SOURCE",
7. "VOLTAGE
BELOW NORMAL OR SHORTED TO LOW SOURCE",
8. "CURRENT
BELOW NORMAL OR OPEN CIRCUIT",
9. "CURRENT
ABOVE NORMAL OR GROUNDED CIRCUIT",
10. "MECHANICAL
SYSTEM NOT RESPONDING OR OUT OF ADJUSTMENT",
11. "ABNORMAL
FREQUENCY OR PULSE WIDTH OR PERIOD",
"ABNORMAL UPDATE RATE",
12. "ABNORMAL
RATE OF CHANGE",
13. "ROOT
CAUSE NOT KNOWN",
14. "BAD
INTELLIGENT DEVICE OR COMPONENT",
15. "OUT
OF CALIBRATION",
16. "SPECIAL
INSTRUCTIONS",
17. "DATA
VALID BUT ABOVE NORM. OPERATIONAL RANGE - LEAST SEVERE LEVEL",
18. "DATA
VALID BUT ABOVE NORM. OPERATIONAL RANGE - MODERATELY SEVERE LEVEL",
19. "DATA
VALID BUT BELOW NORM. OPERATIONAL RANGE - LEAST SEVERE LEVEL",
20. "DATA
VALID BUT BELOW NORM. OPERATIONAL RANGE MODERATELY SEVERE LEVEL",
21. "RECEIVED
NETWORK DATA IN ERROR",
22. "RESERVED
FOR SAE ASSIGNMENT",
23. "NOT
AVAILABLE OR CONDITIONS EXIST",
|
Customer Survey
How are we doing? Please take a moment to fill out our brief (less than a minute) survey.
Take the Survey >
|