iGUARD Troubleshooting
- Problems
with AC voltage
- Problems
with AC current
- Problems
with AC power (kW or kVA)
- Problems
with AC frequency
- Problems
with power factor
Troubleshooting
AC Parameters
CAUTION: LETHAL
VOLTAGES AND CURRENTS MAY BE PRESENT!!!
All
due caution should be exercised when investigating AC voltage
and current connections. Live AC may - and should always be assumed
to be - present. If you are not totally familiar and conversant
with the necessary precautions and safety practices relevant
to troubleshooting this type of equipment, call a licensed electrician! Voltages
and currents may be present and should be assumed to be at a
lethal potential at all times.
The
most common - by at least a factor of 20 - cause of problems associated
with any of the AC parameters not reading, reading wrong, reading
erratically, or causing nonsense information to be displayed, is
caused by the AC connections not being made correctly. It is easy
to get wrong, but it's also easy to fix!
The
following text descriptions are also accompanied with some 'common'
setups diagrams to help explain and or clarify the details, as
well as make installing and applying the iGUARD easier.
Problems
with AC Voltage - Be
aware that a shutdown for excessive loading, improperly adjusted
governor, or automatic voltage regulator problems (AVR) may give
a message to the effect of over/under voltage as the set hunts
for its proper operating point.
1. No
voltage displayed
a. Alternator
putting out AC voltage?
b. Check
the wire connections from the energy monitoring board to the AC source.
c. Verify
that AC voltage is reaching the plug
d. Check
that the plug is seated in the energy monitor board
e. Is
AC neutral connected?
f. Contact
FWM tech services
2. Shuts
down on under or over voltage at startup
a. AC
voltage present?
b. Measure
actual voltage
c. Below/above
setpoints?
d. Adjust
AC voltage (AVR) or adjust O/U voltage setpoint
e. Verify
that AC neutral is connected to system and is properly bonded to
earth and or generator frame as necessary
3. Shuts
down on over/undervoltage after running for awhile
a. AC
voltage present?
b. Measure
actual voltage
c. Below/above
setpoints?
d. Adjust
AC voltage (AVR) or adjust O/U voltage setpoint
e. Is
set being block loaded or unloaded?
f. Verify
that the generator set is recovering within the programmed warning
timer (one of the last three selections in the AC setup on the iGUARD).
g. Verify
that the AVR is recovering
4. Voltage
reading is wrong
a. Set
for L-L or L-N readings as desired?
b. AC
Neutral in plug and properly bonded to earth?
c. Calibrate
iGUARD voltage reading (see IOM)
Problems
with AC Current
NEVER
UNPLUG THE CURRENT TRANSFORMERS UNDER LOAD. THIS IS POTENTIALLY
LETHAL AND MAY RESULT IN INJURY OR DEATH TO PERSONNEL OR THE
DESTRUCTION OF THE CURRENT TRANSFORMERS
1. No
current displayed
a. Alternator
putting out AC voltage/current?
b. Check
the wire connections from the energy monitoring board to the current
transformer(s).
c. Verify
that AC current is reaching the plug - Check that the plug is seated
in the energy monitor board
d. Is
there actual current demand / load?
2. Shuts
down on overcurrent at start up
a. Adjust
instantaneous overcurrent setpoint
b. Is
generator undersized for load?
3. Shuts
down on overcurrent after running for awhile
a. Is
the overcurrent setting lower than the actual operating current?
b. Is
the load relatively steady or are there large swings?
i. If
the load is relatively steady overcurrent shutdowns can come from
either reaching the instantaneous shutdown point (The max current
setting) or by running at greater than full load longer than the
IDMT constant.
ii. If
there are large swings - rapid block loads and unloads - you may
need to increase either the overcurrent setpoint or the bubble timer
associated with overcurrent events.
c. Is
the CT ratio correct?
4. Reverse
current indicated
a. Swap
(+) and (-) leads on all CT's in system
5. Reverse
current indicated on only one or two phases
a. Physically
verify that AC Volts L1 is connected to L1
b. Physically
verify that AC Volts L2 is connected to L2
c. Physically
verify that AC Volts L3 is connected to L3
d. Physically
verify that AC current CT for L1 is on L1
e. Physically
verify that AC current CT for L2 is on L2
f. Physically
verify that AC current CT for L3 is on L3
g. Physically
verify that all CT's are oriented the same way
6. Current
reading is wrong
a. Is
the reading approximately ½ of correct? Verify how the CT
is connected to the system. If both the CT leads from each CT are
brought back, change CT to Grounded = NO
b. Is
the reading approximately double correct? Verify how the CT is connected
to the system. If only one of the CT leads from each CT is brought
back to the iGUARD , change CT to Grounded = YES
c. Verify
that the voltage and current connections are correct:
i. Physically
verify that AC Volts L1 is connected to L1
ii. Physically
verify that AC Volts L2 is connected to L2
iii. Physically
verify that AC Volts L3 is connected to L3
iv. Physically
verify that AC current CT for L1 is on L1
v. Physically
verify that AC current CT for L2 is on L2
vi. Physically
verify that AC current CT for L3 is on L3
vii. Physically
verify that all CT's are oriented the same way
d. Calibrate
AC current (See IOM)
Problems
with AC Power (kW or kVA)
1. No
power displayed
a. Verify
that the CT's are connected
b. Verify
that the CT's are the proper range (1000:5 vs 100:5 makes a huge
difference!)
c. Is
there a load with current flow in the system?
d. Is
power factor showing PFC2 or PFC3? Load current may be below threshold.
Increase load (if possible) to test
e. Is
the PF showing PFC1 or PFC3? If so the load current may be changing >10%
per measurement, and the iGUARD is forcing the PF to 1.00 until the
data settles out.
2. Shows
wrong value
a. Verify
that the voltage and current connections are correct:
i. Physically
verify that AC Volts L1 is connected to L1
ii. Physically
verify that AC Volts L2 is connected to L2
iii. Physically
verify that AC Volts L3 is connected to L3
iv. Physically
verify that AC current CT for L1 is on L1
v. Physically
verify that AC current CT for L2 is on L2
vi. Physically
verify that AC current CT for L3 is on L3
vii. Physically
verify that all CT's are oriented the same way
b. Is
the PF showing PFC1 or PFC2? If so the load current may be changing >10%
per measurement, and the iGUARD is forcing the PF to 1.00 until the
data settles out.
Problems
with AC frequency
1. Over/under
frequency warnings or shutdowns
a. Is
AC voltage present? (No voltage = no frequency)
b. Check
AC frequency at no load. Should be very close or equal to nominal
c. Check
AC frequency during load. Should be > under frequency setpoint
and < over frequency setpoint
d. Is
governor recovering too slowly?
e. Is
genset too small for load?
f. Is
load noisy?
2. Incorrect
frequency readings
a. Measure
AC frequency & verify
b. Is
load noisy?
c. Check
AC neutral for proper bonding to earth
Problems
with power factor
1. Inaccurate
power factor
a. Verify
that the voltage and current connections are correct:
i. Physically
verify that AC Volts L1 is connected to L1
ii. Physically
verify that AC Volts L2 is connected to L2
iii. Physically
verify that AC Volts L3 is connected to L3
iv. Physically
verify that AC current CT for L1 is on L1
v. Physically
verify that AC current CT for L2 is on L2
vi. Physically
verify that AC current CT for L3 is on L3
vii. Physically
verify that all CT's are oriented the same way
2. Shuts
down on power factor
a. Adjust
power factor limit to 0% and run under load.
i. Is
displayed PF reasonable under load?
ii. If
PF is strange or unreasonable, it is virtually certain that the AC
voltage and/or current is not connected in proper sequence. See 1.a above
b. Adjust
PF limit to meet actual operating conditions
c. Is
PF unstable or greatly in error? Verify that the voltage and current
connections are correct:
i. Physically
verify that AC Volts L1 is connected to L1
ii. Physically
verify that AC Volts L2 is connected to L2
iii. Physically
verify that AC Volts L3 is connected to L3
iv. Physically
verify that AC current CT for L1 is on L1
v. Physically
verify that AC current CT for L2 is on L2
vi. Physically
verify that AC current CT for L3 is on L3
vii. Physically
verify that all CT's are oriented the same way
3. PFC1
warning
a. Power
factor is being forced to 1.00 because the measured value is changing
more than 10% in 6 seconds
b. If
it does not clear in less than ~20 seconds see 1.a above
4. PFC2
warning
a. Power
factor is being forced to 1.00 because the measured AC current is
too low to accurately calculate power factor reliably.
b. As
long as the load current is too low this warning will stay active.
But increasing the load current to > 5% (approximately) of the
full scale CT ratio should clear this error in a few seconds
5. PFC3
warning - Combination of both PFC1 & PFC2
a. Power
factor is being forced to 1.00 because the measured value is changing
more than 10% in 6 seconds AND the measured AC current is too low
to accurately calculate power factor reliably.
b. If
this doesn't resolve itself into either a PFC1 or PFC2 within a few
seconds, see 1.a above